hardware:mould:attic
This is an old revision of the document!
Table of Contents
Old notes for the mould
Controlling loop
There is temperature ramp prepared which controls the heating power of all four heaters between 0 and 100% depending on the Temperatur read on C1.
Run inside a screen session:
/home/pi/python/actor/actor.py
Code can be found here: https://gitlab.rlp.net/bes3-mainz/mogon-testbench/snippets/497
Bare metal controlling of the heaters
HINT: Better use the web interface to get the status and set the heaters power: http://localhost:10001/status.php#page1
Control the heaters be writing them a value in the range 0.00
and 1.00
:
mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer<Dimmer ID 1..4>/set' -m <brightness 0..1.0>
Example:
mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer4/set' -m 0.75
Get the status
mosquitto_sub -h mould-control -t 'homie/fsrcontrol/heater/dimmer1' -t 'homie/fsrcontrol/heater/dimmer2' -t 'homie/fsrcontrol/heater/dimmer3' -t 'homie/fsrcontrol/heater/dimmer4' -v
Switch on all 4 heaters:
mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer1/set' -m 1; mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer2/set' -m 1; mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer3/set' -m 1; mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer4/set' -m 1; echo "done"
Switch off all 4 heaters:
mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer1/set' -m 0; mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer2/set' -m 0; mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer3/set' -m 0; mosquitto_pub -h mould-control -t 'homie/fsrcontrol/heater/dimmer4/set' -m 0; echo "done"